RP Troubleshooting

Guide for RP Troubleshooting


The following are basic troubleshooting scenarios for the reduced pressure principle assembly. They don't represent all situations and may or may not solve any one particular backflow prevention assembly problem in the field. 

Note: when replacing internal components, use only factory parts.



                     Symptom                                                                 Cause


          Relief valve will not open,                                      Leaking #2 shut off valve.
          gauge does not drop to '0'.



          Relief valve will not open,                                      Relief valve stuck 
          gauge drops down to '0'.                                        in closed position. 




          Relief valve opens when testing                            Fouled #2 check valve                                                                            #2 check valve.                                                      or disc compression.                 

                                                                                                                                                                                              


          Relief valve drips constantly                                 
          with apparent first check                                        Fouled #1 check valve. 
          reading less than 5 psi.



          Relief valve drips constantly with                           Fouled relief valve.
          apparent first check reading of                                                                                                                                             5 psi or higher.